Which of the following statements are true in the design of colum

Which of the following statements are true in the design of colum
|

Which of the following statements are true in the design of columns according to IS 456:2000

A. Minimum Area of steel in longitudinal reinforcement is 8 % of Gross area of column

B.  Minimum Area of steel in longitudinal reinforcement is 0.8 % of gross area of column

C. Minimum number of bars for reinforcement in longitudinal reinforcement for rectangular column is 6

D. Maximum area of steel in longitudinal reinforcement when bars are not lapped is 6 % of Gross area of column.

Please scroll down to see the correct answer and solution guide.

Right Answer is:

SOLUTION

Concept

As per IS 456: 2000, clause 26.5.3.1,

Longitudinal reinforcement in a column:

The minimum number of longitudinal bar:

The minimum number of the longitudinal bar provided in column shall be

  • four in rectangular columns
  • six in circular columns

Percentage of steel:

The cross-sectional area of longitudinal reinforcement shall be not less than 0.8 % nor more than 6 % of the gross cross-sectional area of the column. 

The minimum diameter of longitudinal reinforcement bars:

The main longitudinal reinforcement bars used in column shall not be less than 12 mm in diameter.

Helical reinforcement:

A reinforced concrete column having helical reinforcement shall have at least six bar of longitudinal reinforcement within the helical reinforcement.

Spacing:

The spacing of longitudinal bars measured along the periphery of the column shall not exceed 300 mm.

 ∴  Option 2 and 4 are correct